Apollo 2B6K-L 6000VA Online UPS

  • Input: Nominal Voltage: 220VAC, Voltage Range: 176~276VAC, Frequency Range: 46~54Hz (default), user adjustable within 40~60Hz, Power Factor: 0.97
  • Output: Voltage: 220VAC ± 1%, Frequency: 46-54Hz ± 0.2Hz (Line mode), 50Hz ± 0.2Hz (battery mode), Waveform: Sine wave, Distortion: ≤2% under linear load, Power Factor: 0.7, Overload capability: 108%~150% for 30 seconds, ±150% for 300ms, Current Crest Ratio: 3:1
  • Battery: Type: Sealed, Maintenance free, Lead-Acid, Recharge Time: 8hrs to 90% of capacity after full load discharge
  • Bypass: Automatic Transfer: on overload and UPS failure, Before UPS power-on: Default “NO”, user adjustable to “YES”, Transfer time: 0ms; less than 4 ms from inverter to bypass and vice versa
  • LED/LCD Indicators: Status: load level/Battery level, Battery, Utility power, Inverter, Bypass, Overload, Fault, Audible Alarm: Bypass, ON battery mode, Battery low, Overload, Fault
  • Acoustic Noise: At 1 meter distance: 55 dBA
  • Communications: DB-9 Port: RS-232 Serial Interface, Intelligent Slot: Options; Webpowet, As400 Card or WinPower CMC
  • Environmental: Operating Temperature: 0-40℃, Operating Humidity: 20~90% non-condensing, Weight: 90/35, Dimensions: 260570717

Share on:

Nationwide Delivery

We deliver your orders anywhere in the country, quickly and securely.

Official Warranty

We offer official warranties and quick after-sales service.

Secure Payment

Your money's safe with us when you buy, no need to worry.

Product Description

 

Feature Description
Input
  • Nominal Voltage: 220VAC
  • Voltage Range: 176~276VAC
  • Frequency Range: 46~54Hz (default), user adjustable within 40~60Hz
  • Power Factor: 0.97
Output
  • Voltage: 220VAC ± 1%
  • Frequency: 46-54Hz ± 0.2Hz (Line mode), 50Hz ± 0.2Hz (battery mode)
  • Waveform: Sine wave
  • Distortion: ≤2% under linear load
  • Power Factor: 0.7
  • Overload capability: 108%~150% for 30 seconds, ±150% for 300ms
  • Current Crest Ratio: 3:1